Clēēr™ Loadbreak Connector reduces outages by providing reliable switching under load – as reliable as traditional 200A loadbreak connectors – and allows other circuits to remain energized, limiting the amount of downtime and inconvenienced customers.
It is the only 600A/15 kV three-phase rated loadbreak connector system in the industry. This unique solution offers both a visible break and visible ground without having to de-energize, unbolt 600A terminations, or move heavy cables. This system offers an efficient and reliable visible break when used for sectionalizing, splicing, or in-line with vacuum switchgear.
| Continuous Current | 600 A rms |
| Loadbreak Switching | Ten make and break operations at 600 A at 14.4 kV Phase-Phase |
| Loadbreak Switching | Three make and break operations at 900 A at 14.4 kV Phase-Phase |
| Fault Closure | 16 kA rms symmetrical at 14.4 kV Phase-Phase after ten 600 A loadbreak switching operations for 0.17 seconds |
| Fault Closure | 16 kA rms symmetrical at 14.4 kV Phase-Phase after three 900 A loadbreak switching operations for 0.17 seconds |
| 4 Hour Overload Current | 900 A rms |
| Short Time Current | 16 kA rms symmetrical for 0.17 seconds (limited by fault closure rating) |
| Short Time Current | 10 kA rms symmetrical for 3.0 seconds |